Viessmann · Heat pump

PC01 Overvoltage or low voltage protection

High severity DLFSHCVitocal IND-H

What the control is telling you

Abnormal rises or drops in supply voltage are detected by the voltage detection circuit.

Applies to: Outdoor unit supply voltage monitoring

Likely causes

  • Faulty power supply
  • Faulty or loose power supply wires
  • Faulty IPM module board
  • Faulty reactor
  • Faulty PCB

Test and repair steps

  1. Check the power supply and confirm it is in working order.
  2. Turn off the unit.
  3. Check the connections and wires; fix or replace as needed.
  4. Power on and measure voltage between P and N; in standby it should be about DC 310 V, 340 V or 380 V.
  5. At unit start-up, confirm the voltage is 220 V to 400 V.
  6. If the voltage is wrong, check the reactor and replace it if faulty.
  7. Replace the IPM board or outdoor PCB if the fault remains.

Other codes on the same units

  • EH03 Indoor fan speed outside normal range
  • EH06 Indoor PCB and display board communication error
  • EH60 Indoor temperature sensor open or short circuit (T1, T2)
  • EL0C Refrigerant leakage detection
  • EL01 Indoor and outdoor unit communication error
  • PC00 IPM malfunction or IGBT over-strong current protection
  • PC02 Compressor top temperature or IPM high temperature / high pressure protection
  • PC08 Current overload protection

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: DLFSHC Service Manual, p. 31. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.