Viessmann · Heat pump

PC08 Current overload protection

High severity DLFSHCVitocal IND-H

What the control is telling you

An abnormal current rise is detected by the outdoor current detection circuit.

Applies to: Outdoor unit current protection

Likely causes

  • Unstable or abnormal supply voltage
  • Incorrect L and N wiring
  • Faulty reactor
  • Outdoor fan fault
  • Dirty heat exchanger or poor ventilation
  • Overcharged refrigerant system
  • Faulty outdoor main PCB

Test and repair steps

  1. Check whether the protection activated in standby mode.
  2. Check that the power voltage is normal and the power wiring is correct; reconnect L and N if needed.
  3. Measure voltage between P and N in standby; it should be about DC 310 V, 340 V or 380 V.
  4. At start-up, confirm the voltage is in the 220 V to 400 V range.
  5. Check the reactor wiring and that the reactor and inductance work normally; replace the reactor if faulty.
  6. Check that the outdoor ambient is not above 50 °C and that the outdoor unit ventilation works.
  7. Check the outdoor fan; see the fan speed out-of-range fault.
  8. Clean the heat exchanger if dirty.
  9. Check system pressure; if too high, recover the overcharged refrigerant.
  10. If the fault persists, replace the outdoor main board.

Other codes on the same units

  • EH03 Indoor fan speed outside normal range
  • EH06 Indoor PCB and display board communication error
  • EH60 Indoor temperature sensor open or short circuit (T1, T2)
  • EL0C Refrigerant leakage detection
  • EL01 Indoor and outdoor unit communication error
  • PC00 IPM malfunction or IGBT over-strong current protection
  • PC01 Overvoltage or low voltage protection
  • PC02 Compressor top temperature or IPM high temperature / high pressure protection

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: DLFSHC Service Manual, p. 27. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.