Viessmann · Heat pump
PC08 Current overload protection
What the control is telling you
An abnormal current rise is detected by the outdoor current detection circuit.
Applies to: Outdoor unit current protection
Likely causes
- Unstable or abnormal supply voltage
- Incorrect L and N wiring
- Faulty reactor
- Outdoor fan fault
- Dirty heat exchanger or poor ventilation
- Overcharged refrigerant system
- Faulty outdoor main PCB
Test and repair steps
- Check whether the protection activated in standby mode.
- Check that the power voltage is normal and the power wiring is correct; reconnect L and N if needed.
- Measure voltage between P and N in standby; it should be about DC 310 V, 340 V or 380 V.
- At start-up, confirm the voltage is in the 220 V to 400 V range.
- Check the reactor wiring and that the reactor and inductance work normally; replace the reactor if faulty.
- Check that the outdoor ambient is not above 50 °C and that the outdoor unit ventilation works.
- Check the outdoor fan; see the fan speed out-of-range fault.
- Clean the heat exchanger if dirty.
- Check system pressure; if too high, recover the overcharged refrigerant.
- If the fault persists, replace the outdoor main board.
Other codes on the same units
- EH03 Indoor fan speed outside normal range
- EH06 Indoor PCB and display board communication error
- EH60 Indoor temperature sensor open or short circuit (T1, T2)
- EL0C Refrigerant leakage detection
- EL01 Indoor and outdoor unit communication error
- PC00 IPM malfunction or IGBT over-strong current protection
- PC01 Overvoltage or low voltage protection
- PC02 Compressor top temperature or IPM high temperature / high pressure protection
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: DLFSHC Service Manual, p. 27. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.