Viessmann · Heat pump
EC07 Outdoor fan speed outside normal range
What the control is telling you
The outdoor fan speed stays too low or too high for a set time. The unit shows the failure code and the AC turns off.
Applies to: DLFSHC outdoor unit. On some models the outdoor PCB cannot be removed separately and the control box is replaced as a whole.
Likely causes
- Outdoor fan motor fault
- Fan assembly binding
- Fan motor wiring fault
- Outdoor main PCB fault
Test and repair steps
- Power off. After two minutes, turn the unit on. If the code clears, the unit is normal.
- If it remains, shut off the power and rotate the fan by hand.
- If the fan does not turn easily, find and fix the cause.
- Check the fan motor wiring and make sure the connections are proper.
- Measure the fan motor voltage from the PCB. If it is wrong, replace the outdoor main PCB.
- If the voltage is correct, replace the fan motor.
Other codes on the same units
- EC51 Outdoor EEPROM parameter error or compressor driven chip EEPROM parameter error
- EC53 Outdoor temperature sensor open or short circuit (T3, T4, TP, T2B, TH)
- EH02 Zero crossing detection error
- EH03 Indoor fan speed outside normal range
- EH06 Indoor PCB and display board communication error
- EH60 Indoor temperature sensor open or short circuit (T1, T2)
- EL0C Refrigerant leakage detection
- EL01 Indoor and outdoor unit communication error
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Viessmann Vitocal IND-H DLFSHC service manual, p. 21. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.