Viessmann · Heat pump
PC 0F PFC module protection
What the control is telling you
The voltage signal the IPM sends to the compressor drive chip is abnormal. The LED shows the failure and the unit turns off.
Applies to: DLCLRC outdoor units 36, 48, 58
Likely causes
- Shorted IPM output or PFC module
- Loose connection between main board and PFC module
- Faulty PFC inductance
- Faulty outdoor main PCB
Test and repair steps
- Measure resistance between every two of U, V, W of the IPM and between P and N. If any reading is 0 or close to 0, the IPM is defective.
- Check that the connecting line between the main board and the PFC module is tight. Reconnect it if loose.
- Measure the voltage between P and N and compare it to the index.
- Check the PFC inductance. If it reads 0 between its two ports, replace the inductance.
- If the inductance is good, replace the outdoor main board.
- If the fault remains, replace the PFC module.
Models that show this code
22 models in Vitocal 100-S
Other codes on the same units
- PC 06 Discharge temperature protection of compressor
- PC 08 Current overload protection
- PC 0A High temperature protection of condenser
- PC 30 High pressure protection
- PC 31 Low pressure protection
- PC 40 Communication error between outdoor main PCB and IPM board
- PC 41 Outdoor compressor current sampling circuit failure
- PC 43 Outdoor compressor lack phase protection
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: DLCLRC Service Manual, p. 30. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.