Viessmann · Heat pump

PC 06 Discharge temperature protection of compressor

High severity Vitocal 100-S

What the control is telling you

The compressor discharge temperature stays above a set level for nine seconds. The compressor stops and the LED shows the failure.

Applies to: DLCLRC outdoor units 36, 48, 58

Likely causes

  • Refrigerant leak and low charge
  • Wrong or loose discharge temperature sensor wiring
  • Faulty discharge temperature sensor
  • Faulty high pressure valve assembly
  • Faulty outdoor main PCB

Test and repair steps

  1. Check whether refrigerant is leaking. If so, stop the leak and add refrigerant.
  2. Check that the compressor discharge sensor and PCB are wired per the wiring diagram. Correct any wiring fault.
  3. Check whether discharge temperature is above 115 °C (R410A) or 108 °C (R32).
  4. If the value is normal, measure the discharge temperature sensor resistance. Replace the sensor if it is faulty.
  5. If the high pressure valve path in the flowchart applies, replace the high pressure valve assembly.
  6. If the fault remains, replace the outdoor main PCB.

Models that show this code

22 models in Vitocal 100-S

06AAK09AAK12AAJ12AAK18AAK24AAK30AAKDLCLRCQ36AA3DLCLRCQ48AA3DLCLRCQ58AA3DLCURAQ18AA3DLCURAQ18AB3DLCURAQ24AA3DLCURAQ24AB3DLCURAQ30AA3DLCURAQ30AB3DLCURAQ36AA3DLCURAQ36AB3DLCURAQ48AA3DLCURAQ48AB3DLCURAQ60AA3DLCURAQ60AB3

Other codes on the same units

  • LC 06 IPM module high temperature protection
  • PC 08 Current overload protection
  • PC 0A High temperature protection of condenser
  • PC 0F PFC module protection
  • PC 30 High pressure protection
  • PC 31 Low pressure protection
  • PC 40 Communication error between outdoor main PCB and IPM board
  • PC 41 Outdoor compressor current sampling circuit failure

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: DLCLRC Service Manual, p. 28. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.