Viessmann · Heat pump
PC 31 Low pressure protection
What the control is telling you
Low refrigerant pressure protection has tripped, reported as PC 31.
Applies to: DLCURA outdoor units
Likely causes
- Connection wires to the low pressure protector
- Low pressure protector
- Indoor fan assembly
- Outdoor main PCB
- Low refrigerant charge
- Closed high pressure valve
Test and repair steps
- Check that the low pressure protector and main board are wired correctly; reconnect if not.
- Measure the low pressure protector resistance with the plug disconnected; replace it if it is not normal.
- Check that the high pressure valve core is fully open; open it if not.
- Check that the indoor fan runs properly in cooling mode; see the fan speed out-of-control solution.
- Check the refrigerant system; if charge is low, add refrigerant and confirm normal operation.
- Replace the outdoor main board if the problem remains.
Models that show this code
22 models in Vitocal 100-S
Other codes on the same units
- PC 0F PFC module protection
- PC 30 High pressure protection
- PC 40 Communication error between outdoor main PCB and IPM board
- PC 41 Outdoor compressor current sampling circuit failure
- PC 43 Outdoor compressor lack phase protection
- PC 44 Outdoor unit zero speed protection
- PC 45 Outdoor unit IR chip drive failure
- PC 46 Compressor speed out of control
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: DLCURA Service Manual, p. 35. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.