Viessmann · Heat pump
PC 44 Outdoor unit zero speed protection
What the control is telling you
The outdoor unit detects a zero-speed fault condition during operation.
Applies to: DLCURA outdoor units
Likely causes
- Connection wires or power wiring
- Bridge rectifier
- PFC circuit or reactor
- Blocked refrigerant piping
- Pressure switch
- Outdoor fan
- IPM module board
- Outdoor PCB
Test and repair steps
- Check whether the protection activated in standby; check input voltage and current.
- Check power voltage and the voltage between L and N; reconnect wiring if not normal.
- Check the bridge rectifier and reactor or inductance; repair or replace if faulty.
- Check outdoor ventilation, the heat exchanger and the outdoor fan.
- Check the refrigerant system and system pressure; recharge per the installation instructions if pressure is too high.
- Replace the outdoor main board if the problem remains.
Models that show this code
22 models in Vitocal 100-S
Other codes on the same units
- PC 30 High pressure protection
- PC 31 Low pressure protection
- PC 40 Communication error between outdoor main PCB and IPM board
- PC 41 Outdoor compressor current sampling circuit failure
- PC 43 Outdoor compressor lack phase protection
- PC 45 Outdoor unit IR chip drive failure
- PC 46 Compressor speed out of control
- PC 49 Compressor overcurrent failure
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: DLCURA Service Manual, p. 38. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.