Viessmann · Heat pump
PC 40 Communication error between outdoor main PCB and IPM board
What the control is telling you
The main PCB cannot detect the IPM board.
Applies to: DLCLRC outdoor unit
Likely causes
- No LED lit on the IPM board
- Faulty or loose signal wire between IPM board and main board
- Faulty IPM board
- Faulty outdoor main board
- Faulty electric control box
Test and repair steps
- Check whether at least one LED on the IPM board is lit. If none is lit, replace the IPM board.
- Check the signal wire between the IPM board and the main board. Reconnect it and retry.
- If the error still appears, replace the IPM board and check whether the system runs normally.
- If the error still appears, replace the outdoor main board and check whether the system runs normally.
- If the error still appears, replace the electric control box.
Models that show this code
22 models in Vitocal 100-S
Other codes on the same units
- PC 30 High pressure protection
- PC 31 Low pressure protection
- PC 41 Outdoor compressor current sampling circuit failure
- PC 43 Outdoor compressor lack phase protection
- PC 44 Outdoor unit zero speed protection
- PC 45 Outdoor unit IR chip drive failure
- PC 46 Compressor speed out of control
- PC 49 Compressor overcurrent failure
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: DLCLRC Service Manual, p. 34. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.