Viessmann · Heat pump

PC 40 Communication error between outdoor main PCB and IPM board

High severity Vitocal 100-S

What the control is telling you

The main PCB cannot detect the IPM board.

Applies to: DLCLRC outdoor unit

Likely causes

  • No LED lit on the IPM board
  • Faulty or loose signal wire between IPM board and main board
  • Faulty IPM board
  • Faulty outdoor main board
  • Faulty electric control box

Test and repair steps

  1. Check whether at least one LED on the IPM board is lit. If none is lit, replace the IPM board.
  2. Check the signal wire between the IPM board and the main board. Reconnect it and retry.
  3. If the error still appears, replace the IPM board and check whether the system runs normally.
  4. If the error still appears, replace the outdoor main board and check whether the system runs normally.
  5. If the error still appears, replace the electric control box.

Models that show this code

22 models in Vitocal 100-S

06AAK09AAK12AAJ12AAK18AAK24AAK30AAKDLCLRCQ36AA3DLCLRCQ48AA3DLCLRCQ58AA3DLCURAQ18AA3DLCURAQ18AB3DLCURAQ24AA3DLCURAQ24AB3DLCURAQ30AA3DLCURAQ30AB3DLCURAQ36AA3DLCURAQ36AB3DLCURAQ48AA3DLCURAQ48AB3DLCURAQ60AA3DLCURAQ60AB3

Other codes on the same units

  • PC 30 High pressure protection
  • PC 31 Low pressure protection
  • PC 41 Outdoor compressor current sampling circuit failure
  • PC 43 Outdoor compressor lack phase protection
  • PC 44 Outdoor unit zero speed protection
  • PC 45 Outdoor unit IR chip drive failure
  • PC 46 Compressor speed out of control
  • PC 49 Compressor overcurrent failure

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: DLCLRC Service Manual, p. 34. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.