Viessmann · Heat pump

PC 46 Compressor speed out of control

High severity Vitocal 100-S

What the control is telling you

Compressor speed has gone outside its controlled range.

Applies to: DLCURA outdoor units

Likely causes

  • Connection wires or power wiring
  • Bridge rectifier
  • PFC circuit or reactor
  • Blocked refrigerant piping
  • Pressure switch
  • Outdoor fan
  • IPM module board
  • Outdoor PCB

Test and repair steps

  1. Check whether the protection activated in standby; check input voltage and current.
  2. Check power voltage and the voltage between L and N; reconnect wiring if not normal.
  3. Check the bridge rectifier and reactor or inductance; repair or replace if faulty.
  4. Check outdoor ventilation, the heat exchanger and the outdoor fan.
  5. Check the refrigerant system and system pressure; recharge per the installation instructions if pressure is too high.
  6. Replace the outdoor main board if the problem remains.

Models that show this code

22 models in Vitocal 100-S

06AAK09AAK12AAJ12AAK18AAK24AAK30AAKDLCLRCQ36AA3DLCLRCQ48AA3DLCLRCQ58AA3DLCURAQ18AA3DLCURAQ18AB3DLCURAQ24AA3DLCURAQ24AB3DLCURAQ30AA3DLCURAQ30AB3DLCURAQ36AA3DLCURAQ36AB3DLCURAQ48AA3DLCURAQ48AB3DLCURAQ60AA3DLCURAQ60AB3

Other codes on the same units

  • PC 30 High pressure protection
  • PC 31 Low pressure protection
  • PC 40 Communication error between outdoor main PCB and IPM board
  • PC 41 Outdoor compressor current sampling circuit failure
  • PC 43 Outdoor compressor lack phase protection
  • PC 44 Outdoor unit zero speed protection
  • PC 45 Outdoor unit IR chip drive failure
  • PC 49 Compressor overcurrent failure

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: DLCURA Service Manual, p. 38. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.