Viessmann · Heat pump

PC 43 Outdoor compressor lack phase protection

High severity Vitocal 100-S

What the control is telling you

The three-phase sampled current to the compressor is abnormal. One or more phases stay very low, close to 0.

Applies to: DLCLRC outdoor unit

Likely causes

  • Open circuit in the compressor three-phase output
  • Loose or faulty compressor connecting lines
  • Unbalanced compressor three-phase resistance
  • Faulty compressor
  • Faulty main PCB

Test and repair steps

  1. Check the compressor three-phase output for an obvious open circuit.
  2. Power off, then restart the unit 2 minutes later. If the code is gone, the unit operates normally.
  3. If the code remains, check both ends of the compressor connecting lines. Correct the connections if they are not good.
  4. Check whether the three-phase resistance of the compressor is symmetrical. Replace the compressor if it is not.
  5. If the resistances are symmetrical and the code remains, replace the main PCB.

Models that show this code

22 models in Vitocal 100-S

06AAK09AAK12AAJ12AAK18AAK24AAK30AAKDLCLRCQ36AA3DLCLRCQ48AA3DLCLRCQ58AA3DLCURAQ18AA3DLCURAQ18AB3DLCURAQ24AA3DLCURAQ24AB3DLCURAQ30AA3DLCURAQ30AB3DLCURAQ36AA3DLCURAQ36AB3DLCURAQ48AA3DLCURAQ48AB3DLCURAQ60AA3DLCURAQ60AB3

Other codes on the same units

  • PC 30 High pressure protection
  • PC 31 Low pressure protection
  • PC 40 Communication error between outdoor main PCB and IPM board
  • PC 41 Outdoor compressor current sampling circuit failure
  • PC 44 Outdoor unit zero speed protection
  • PC 45 Outdoor unit IR chip drive failure
  • PC 46 Compressor speed out of control
  • PC 49 Compressor overcurrent failure

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: DLCLRC Service Manual, p. 35. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.