Viessmann · Heat pump
PC 43 Outdoor compressor lack phase protection
What the control is telling you
The three-phase sampled current to the compressor is abnormal. One or more phases stay very low, close to 0.
Applies to: DLCLRC outdoor unit
Likely causes
- Open circuit in the compressor three-phase output
- Loose or faulty compressor connecting lines
- Unbalanced compressor three-phase resistance
- Faulty compressor
- Faulty main PCB
Test and repair steps
- Check the compressor three-phase output for an obvious open circuit.
- Power off, then restart the unit 2 minutes later. If the code is gone, the unit operates normally.
- If the code remains, check both ends of the compressor connecting lines. Correct the connections if they are not good.
- Check whether the three-phase resistance of the compressor is symmetrical. Replace the compressor if it is not.
- If the resistances are symmetrical and the code remains, replace the main PCB.
Models that show this code
22 models in Vitocal 100-S
Other codes on the same units
- PC 30 High pressure protection
- PC 31 Low pressure protection
- PC 40 Communication error between outdoor main PCB and IPM board
- PC 41 Outdoor compressor current sampling circuit failure
- PC 44 Outdoor unit zero speed protection
- PC 45 Outdoor unit IR chip drive failure
- PC 46 Compressor speed out of control
- PC 49 Compressor overcurrent failure
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: DLCLRC Service Manual, p. 35. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.