Viessmann · Heat pump

PC 45 Outdoor unit IR chip drive failure

High severity Vitocal 100-SDLCURA

What the control is telling you

The IR chip detects an error in its own parameters. The code is shown at power-on.

Applies to: DLCURA outdoor units, models 18AAK to 60ABK

Likely causes

  • Faulty inverter module PCB

Test and repair steps

  1. Power off, then restart the unit 2 minutes later.
  2. If the code remains, replace the inverter module PCB.

Models that show this code

22 models in Vitocal 100-S, DLCURA

06AAK09AAK12AAJ12AAK18AAK24AAK30AAKDLCLRCQ36AA3DLCLRCQ48AA3DLCLRCQ58AA3DLCURAQ18AA3DLCURAQ18AB3DLCURAQ24AA3DLCURAQ24AB3DLCURAQ30AA3DLCURAQ30AB3DLCURAQ36AA3DLCURAQ36AB3DLCURAQ48AA3DLCURAQ48AB3DLCURAQ60AA3DLCURAQ60AB3

Other codes on the same units

  • PC 30 High pressure protection
  • PC 31 Low pressure protection
  • PC 40 Communication error between outdoor main PCB and IPM board
  • PC 41 Outdoor compressor current sampling circuit failure
  • PC 43 Outdoor compressor lack phase protection
  • PC 44 Outdoor unit zero speed protection
  • PC 46 Compressor speed out of control
  • PC 49 Compressor overcurrent failure

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Vitocal 100-S DLCURA service manual, PDF p. 43. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.