Viessmann · Heat pump

PC 0A High temperature protection of condenser

High severity Vitocal 100-S

What the control is telling you

The outdoor pipe temperature is above 65 °C and the unit stops. It restarts only when the pipe temperature drops below 52 °C.

Applies to: DLCLRC outdoor units 36, 48, 58

Likely causes

  • Faulty condenser temperature sensor or its connection
  • Outdoor ambient above 50 °C (54 °C for tropical models)
  • Blocked outdoor ventilation or dirty heat exchanger
  • Low refrigerant charge
  • Faulty outdoor fan or outdoor main board

Test and repair steps

  1. Check whether the condenser temperature is above 65 °C.
  2. Measure the condenser temperature sensor resistance. Replace the sensor if it is out of range.
  3. Check the sensor connection to the PCB. Correct it if needed.
  4. If outdoor ambient is above the limit, stop the unit.
  5. Make sure outdoor ventilation works and clean the heat exchanger if dirty.
  6. Check the refrigerant system. If charge is low, add refrigerant and confirm the system runs.
  7. Check the outdoor fan. If it is faulty, use the fan speed out-of-range solution.
  8. If the fault remains, replace the outdoor main board.

Models that show this code

22 models in Vitocal 100-S

06AAK09AAK12AAJ12AAK18AAK24AAK30AAKDLCLRCQ36AA3DLCLRCQ48AA3DLCLRCQ58AA3DLCURAQ18AA3DLCURAQ18AB3DLCURAQ24AA3DLCURAQ24AB3DLCURAQ30AA3DLCURAQ30AB3DLCURAQ36AA3DLCURAQ36AB3DLCURAQ48AA3DLCURAQ48AB3DLCURAQ60AA3DLCURAQ60AB3

Other codes on the same units

  • PC 06 Discharge temperature protection of compressor
  • PC 08 Current overload protection
  • PC 0F PFC module protection
  • PC 30 High pressure protection
  • PC 31 Low pressure protection
  • PC 40 Communication error between outdoor main PCB and IPM board
  • PC 41 Outdoor compressor current sampling circuit failure
  • PC 43 Outdoor compressor lack phase protection

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: DLCLRC Service Manual, p. 29. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.