Viessmann · Heat pump
PC 08 Current overload protection
What the control is telling you
An abnormal current rise is detected by the current detection circuit.
Applies to: DLCURA outdoor units
Likely causes
- Connection wires or power wiring
- Bridge rectifier
- PFC circuit or reactor
- Blocked refrigerant piping
- Pressure switch
- Outdoor fan
- IPM module board
- Outdoor PCB
- High system pressure
Test and repair steps
- Check whether the protection activated in standby; if so, check the input voltage and current.
- Check that the power voltage and the voltage between L and N are normal; reconnect power wiring if not.
- Check the bridge rectifier input and wiring; reconnect or replace it if faulty.
- Replace the PFC module if not already done.
- Check the reactor or inductance wiring and function; replace it if faulty.
- Check the outdoor ambient temperature; the unit should stop if it is higher than 122 °F (50 °C).
- Check outdoor ventilation and clean the heat exchanger if dirty.
- Check the outdoor fan; see the fan speed solution if faulty.
- If system pressure is too high, recover the refrigerant and recharge per the installation instructions.
- Replace the outdoor main board if the problem remains.
Models that show this code
22 models in Vitocal 100-S
Other codes on the same units
- PC 06 Discharge temperature protection of compressor
- PC 0A High temperature protection of condenser
- PC 0F PFC module protection
- PC 30 High pressure protection
- PC 31 Low pressure protection
- PC 40 Communication error between outdoor main PCB and IPM board
- PC 41 Outdoor compressor current sampling circuit failure
- PC 43 Outdoor compressor lack phase protection
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: DLCURA Service Manual, p. 38. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.