LC 06 IPM module high temperature protection
What the control is telling you
The IPM module temperature is above the set limit.
Applies to: DLCURA outdoor units
Likely causes
- Blocked indoor or outdoor airflow
- Loose PCB or IPM heat sink screws
- Refrigerant system fault
- Outdoor control PCB
- Connection wires
Test and repair steps
- Check indoor and outdoor airflow; clear the air inlets, outlets or heat exchangers.
- Turn the power off and back on after 10 minutes.
- Check the PCB and IPM heat sink screws; tighten them and apply non-conductive heat transfer paste.
- Check the refrigerant system and repair it if faulty.
- Replace the outdoor control PCB if the problem remains.
Models that show this code
22 models in Vitocal 100-S
Other codes on the same units
- EH 65 Open or short circuit of temperature sensor
- EL 16 Communication malfunction between adapter board and outdoor main board
- FC FC display (normal)
- FL 09 Indoor and outdoor unit mismatch
- PC 06 Discharge temperature protection of compressor
- PC 08 Current overload protection
- PC 0A High temperature protection of condenser
- PC 0F PFC module protection
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: DLCURA Service Manual, p. 34. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.