E8 Input overcurrent

High severity Daikin FTX-W

What the control is telling you

Input current is above about 20 A for 2.5 seconds while the compressor runs. The limit drops at high outdoor temperature.

Applies to: FTX30/36WVJU9 with RX30/36WMVJU9 or RK30/36WMVJU9

Likely causes

  • Outdoor temperature out of range
  • Faulty compressor
  • Faulty power module
  • Faulty outdoor PCB
  • Short circuit or wrong internal wiring

Test and repair steps

  1. Turn off power at the disconnect before opening the unit or touching connectors. If parts were swapped, check the internal wiring again.
  2. Disconnect U, V, W and test with the inverter analyzer (check no. 15).
  3. Check the installation (check no. 17) and the discharge pressure (check no. 18).
  4. Replace the outdoor main PCB if the analyzer shows an unlit LED.

Models that show this code

6 models in Daikin FTX-W

FTX30WVJU9FTX36WVJU9RK30WMVJU9RK36WMVJU9RX30WMVJU9RX36WMVJU9

Other codes on the same units

  • E3 High pressure switch tripped
  • E5 Compressor overload (OL) tripped
  • E6 Compressor lock
  • E7 Outdoor DC fan lock
  • F3 Discharge pipe temperature too high
  • F6 High pressure control in cooling
  • F8 Compressor temperature abnormality shutdown
  • H0 Compressor current sensor abnormality

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Daikin FTX-W service manual SiUS042228E, Troubleshooting 4.15, p.89. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.