E3 High pressure switch tripped

High severity Daikin FTX-W

What the control is telling you

The S1PH high pressure switch opened. It opens at 4.15 MPa (602 psi) and resets at 3.2 MPa (464 psi). Shows only on system shutdown.

Applies to: FTX30/36WVJU9 with RX30/36WMVJU9 or RK30/36WMVJU9

Likely causes

  • Closed stop valve
  • Connector S40 loose
  • Switch terminals loose
  • Broken switch harness
  • Faulty S1PH
  • Faulty outdoor PCB

Test and repair steps

  1. Turn off power at the disconnect before opening the unit or touching connectors. Make sure both stop valves are open.
  2. Check connector S40 is seated.
  3. Unplug S40 and read pins 1-2. Near 0 ohms: replace the outdoor main PCB. Infinite: go on.
  4. Disconnect the switch terminals and read across the switch. Near 0 ohms: replace the harness. Infinite: replace the S1PH.

Models that show this code

6 models in Daikin FTX-W

FTX30WVJU9FTX36WVJU9RK30WMVJU9RK36WMVJU9RX30WMVJU9RX36WMVJU9

Other codes on the same units

  • A6 Indoor fan motor (DC) abnormality
  • C4 Indoor coil thermistor fault
  • C9 Room temperature thermistor fault
  • E1 Outdoor PCB abnormality
  • E5 Compressor overload (OL) tripped
  • E6 Compressor lock
  • E7 Outdoor DC fan lock
  • E8 Input overcurrent

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Daikin FTX-W service manual SiUS042228E, Troubleshooting 4.11, p.83. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.