Daikin · Mini-split
E1 Outdoor PCB abnormality
What the control is telling you
The outdoor microcomputer is not running properly or no zero-cross signal is seen.
Applies to: FTX30/36WVJU9 with RX30/36WMVJU9 or RK30/36WMVJU9
Likely causes
- Faulty outdoor PCB
- Electrical noise
- Momentary voltage drop or power loss
Test and repair steps
- Turn off power at the disconnect before opening the unit or touching connectors. Check the outdoor unit is grounded.
- Power on again and look at LED A (wait 15 seconds, start fan mode from the remote first). Blinking: ground problem or zero-cross fault, replace the main PCB if it persists. Steady on or off: replace the outdoor main PCB.
Models that show this code
6 models in Daikin FTX-W
Other codes on the same units
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Daikin FTX-W service manual SiUS042228E, Troubleshooting 4.10, p.82. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.