Daikin · Mini-split
A6 Indoor fan motor (DC) abnormality
What the control is telling you
Fan speed stays below the target and under 50% of maximum, as read from the Hall IC.
Applies to: FTX30/36WVJU9 with RX30/36WMVJU9 or RK30/36WMVJU9
Likely causes
- Large supply voltage drop
- Shorted or open motor winding
- Broken motor lead
- Faulty motor capacitor
- Faulty indoor PCB
Test and repair steps
- Turn off power at the disconnect before opening the unit or touching connectors. Check supply voltage is within 10% of rated.
- Spin the fan by hand. If it binds, replace the fan motor.
- With the motor connector unplugged and power on, measure the connector: motor supply 310 to 340 VDC (pins 4-7), control voltage 15 VDC (pins 4-3), speed command 1 to 6.5 VDC (pins 4-2). A missing value points to the indoor PCB.
- Reconnect with power off, run, and check for rotation pulses (pins 4-1). No pulses: replace the motor. Otherwise replace the indoor PCB.
Models that show this code
6 models in Daikin FTX-W
Other codes on the same units
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Daikin FTX-W service manual SiUS042228E, Troubleshooting 4.4, p.72. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.