Daikin · Mini-split

A1 Indoor PCB abnormality

High severity Daikin FTX-W

What the control is telling you

The indoor microcomputer cannot complete its internal settings.

Applies to: FTX30/36WVJU9 with RX30/36WMVJU9 or RK30/36WMVJU9

Likely causes

  • Wrong models connected
  • Faulty indoor PCB
  • Loose connector
  • Low supply voltage

Test and repair steps

  1. Turn off power at the disconnect before opening the unit or touching connectors. Check connectors and harness from the terminal strip to the control PCB (H1, H2, H3). Unplug and reseat them.
  2. Check the supply voltage.
  3. Confirm the indoor and outdoor units are a compatible pair.
  4. If the error repeats, replace the indoor control PCB.

Models that show this code

6 models in Daikin FTX-W

FTX30WVJU9FTX36WVJU9RK30WMVJU9RK36WMVJU9RX30WMVJU9RX36WMVJU9

Other codes on the same units

  • 00 Normal (no fault stored)
  • A5 Freeze-up protection or heating peak-cut
  • A6 Indoor fan motor (DC) abnormality
  • C4 Indoor coil thermistor fault
  • C9 Room temperature thermistor fault
  • E1 Outdoor PCB abnormality
  • E3 High pressure switch tripped
  • E5 Compressor overload (OL) tripped

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Daikin FTX-W service manual SiUS042228E, Troubleshooting 4.2, p.69. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.