Daikin · Mini-split
A5 Freeze-up protection or heating peak-cut
What the control is telling you
In cooling, the indoor coil dropped below 0 C (32 F). In heating, the indoor coil went above 60 C (140 F). Operation is halted to protect the unit.
Applies to: FTX30/36WVJU9 with RX30/36WMVJU9 or RK30/36WMVJU9
Likely causes
- Short-circuited airflow
- Dirty indoor filter
- Dirty indoor coil
- Faulty indoor coil thermistor
- Faulty indoor PCB
Test and repair steps
- Turn off power at the disconnect before opening the unit or touching connectors. Check for blocked airflow and clear it.
- Clean the air filter.
- Clean the indoor coil.
- Check the indoor coil thermistor against the resistance chart (check no. 01).
- If the thermistor is good, replace the indoor control PCB.
Models that show this code
6 models in Daikin FTX-W
Other codes on the same units
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Daikin FTX-W service manual SiUS042228E, Troubleshooting 4.3, p.71. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.