Daikin · Mini-split

E5 Compressor overload (OL) tripped

High severity Daikin FTX-W

What the control is telling you

The compressor OL protector opened (trips at 130 C / 266 F, resets at 95 C / 203 F). Repeats lead to shutdown. The counter resets after about 60 minutes of running without another error. Shows only on system shutdown.

Applies to: FTX30/36WVJU9 with RX30/36WMVJU9 or RK30/36WMVJU9

Likely causes

  • Discharge thermistor off its holder or faulty
  • Connector S40 loose
  • OL (Q1M) terminals loose or OL faulty
  • Broken OL harness
  • Faulty expansion valve or coil
  • Faulty four way valve or coil
  • Faulty outdoor PCB
  • Refrigerant shortage
  • Moisture in refrigerant
  • Faulty stop valve

Test and repair steps

  1. Turn off power at the disconnect before opening the unit or touching connectors. Check the discharge pipe thermistor is in place and reads right (check no. 01).
  2. Check connector S40 and the OL (Q1M) resistance; infinite means a bad OL or harness.
  3. Check the expansion valve (check no. 12) and four way valve (check no. 13).
  4. Check the refrigerant side for shortage, moisture and stop valve condition (check no. 14).
  5. Replace the outdoor main PCB last.

Models that show this code

6 models in Daikin FTX-W

FTX30WVJU9FTX36WVJU9RK30WMVJU9RK36WMVJU9RX30WMVJU9RX36WMVJU9

Other codes on the same units

  • C4 Indoor coil thermistor fault
  • C9 Room temperature thermistor fault
  • E1 Outdoor PCB abnormality
  • E3 High pressure switch tripped
  • E6 Compressor lock
  • E7 Outdoor DC fan lock
  • E8 Input overcurrent
  • F3 Discharge pipe temperature too high

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Daikin FTX-W service manual SiUS042228E, Troubleshooting 4.12, p.84. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.