Daikin · Mini-split

E7 Outdoor DC fan lock

High severity Daikin FTX-W

What the control is telling you

The outdoor fan does not start within 15 to 30 seconds of the motor being driven. Repeats lead to shutdown. Resets after about 11 minutes of error-free running. Shows only on system shutdown.

Applies to: FTX30/36WVJU9 with RX30/36WMVJU9 or RK30/36WMVJU9

Likely causes

  • Fan motor connector off
  • Foreign object in the fan
  • Faulty fan motor
  • Faulty outdoor PCB

Test and repair steps

  1. Turn off power at the disconnect before opening the unit or touching connectors. Check the fan motor connector.
  2. Remove anything blocking the fan.
  3. Run the outdoor fan motor check (check no. 16). Replace the fan motor if the Hall IC pulses are missing, otherwise replace the outdoor main PCB.

Models that show this code

6 models in Daikin FTX-W

FTX30WVJU9FTX36WVJU9RK30WMVJU9RK36WMVJU9RX30WMVJU9RX36WMVJU9

Other codes on the same units

  • E1 Outdoor PCB abnormality
  • E3 High pressure switch tripped
  • E5 Compressor overload (OL) tripped
  • E6 Compressor lock
  • E8 Input overcurrent
  • F3 Discharge pipe temperature too high
  • F6 High pressure control in cooling
  • F8 Compressor temperature abnormality shutdown

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Daikin FTX-W service manual SiUS042228E, Troubleshooting 4.14, p.88. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.