Daikin · Mini-split

E6 Compressor lock

Critical severity Daikin FTX-W

What the control is telling you

A lock is detected from the current waveform when high frequency voltage is applied to the motor. Repeats lead to shutdown. Resets after about 11 minutes of error-free running. Shows only on system shutdown.

Applies to: FTX30/36WVJU9 with RX30/36WMVJU9 or RK30/36WMVJU9

Likely causes

  • Closed stop valve
  • Locked compressor
  • Compressor harness disconnected

Test and repair steps

  1. Turn off power at the disconnect before opening the unit or touching connectors. Open the stop valve if closed.
  2. Disconnect the U, V, W harnesses and test with the inverter analyzer (check no. 15). All LEDs even: replace the compressor. Uneven: check the power module (check no. 22).
  3. Wait 30 seconds after power off before restarting.

Models that show this code

6 models in Daikin FTX-W

FTX30WVJU9FTX36WVJU9RK30WMVJU9RK36WMVJU9RX30WMVJU9RX36WMVJU9

Other codes on the same units

  • C9 Room temperature thermistor fault
  • E1 Outdoor PCB abnormality
  • E3 High pressure switch tripped
  • E5 Compressor overload (OL) tripped
  • E7 Outdoor DC fan lock
  • E8 Input overcurrent
  • F3 Discharge pipe temperature too high
  • F6 High pressure control in cooling

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Daikin FTX-W service manual SiUS042228E, Troubleshooting 4.13, p.87. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.