Daikin · Mini-split

H0 Compressor current sensor abnormality

High severity Daikin FTX-W

What the control is telling you

Pre-start DC current reading is outside 0.5 to 4.5 V, or DC voltage before start is under 50 V.

Applies to: FTX30/36WVJU9 with RX30/36WMVJU9 or RK30/36WMVJU9

Likely causes

  • Broken or loose compressor harness
  • Faulty outdoor PCB

Test and repair steps

  1. Turn off power at the disconnect before opening the unit or touching connectors. Check the compressor relay harness.
  2. Power off and on and restart. If it does not return, it is not a fault.
  3. If it returns and the harness is good, replace the outdoor main PCB.

Models that show this code

6 models in Daikin FTX-W

FTX30WVJU9FTX36WVJU9RK30WMVJU9RK36WMVJU9RX30WMVJU9RX36WMVJU9

Other codes on the same units

  • E8 Input overcurrent
  • F3 Discharge pipe temperature too high
  • F6 High pressure control in cooling
  • F8 Compressor temperature abnormality shutdown
  • H6 Compressor position sensor abnormality (start failure)
  • H8 Current transformer (CT) abnormality
  • H9 Outdoor air thermistor fault
  • J3 Discharge pipe thermistor fault

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Daikin FTX-W service manual SiUS042228E, Troubleshooting 4.20, p.97. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.