Daikin · Mini-split
H6 Compressor position sensor abnormality (start failure)
What the control is telling you
The compressor failed to start properly based on the position detection circuit. Repeats lead to shutdown. Resets after about 11 minutes of error-free running.
Applies to: FTX30/36WVJU9 with RX30/36WMVJU9 or RK30/36WMVJU9
Likely causes
- Supply voltage out of spec
- Compressor harness off
- Faulty compressor
- Faulty outdoor PCB
- Closed stop valve
Test and repair steps
- Turn off power at the disconnect before opening the unit or touching connectors. Check connections and supply voltage (within 10% of rated).
- Disconnect U, V, W and run the inverter analyzer (check no. 15). Even LEDs: compressor bad.
- Check the DC bus capacitor voltage, 320 VDC range (+100/-50), and the diode bridge for shorts (check no. 20).
- Check the discharge pressure (check no. 18) and replace the stop valve if needed.
Models that show this code
6 models in Daikin FTX-W
Other codes on the same units
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Daikin FTX-W service manual SiUS042228E, Troubleshooting 4.21, p.98. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.