Daikin · Mini-split
H8 Current transformer (CT) abnormality
What the control is telling you
Compressor frequency is above 32 Hz while input current is under 0.5 A. Repeats lead to shutdown. Resets after about 60 minutes of error-free running.
Applies to: FTX30/36WVJU9 with RX30/36WMVJU9 or RK30/36WMVJU9
Likely causes
- Faulty power module
- Broken or loose wiring
- Faulty reactor
- Faulty outdoor PCB
Test and repair steps
- Turn off power at the disconnect before opening the unit or touching connectors. Power off and on, then run.
- Check the DC bus capacitor voltage (check no. 21) and supply voltage.
- Disconnect U, V, W and run the inverter analyzer (check no. 15). Uneven LEDs: check the power module. Even LEDs: replace the compressor.
- If nothing else fails, replace the outdoor main PCB.
Models that show this code
6 models in Daikin FTX-W
Other codes on the same units
- F6 High pressure control in cooling
- F8 Compressor temperature abnormality shutdown
- H0 Compressor current sensor abnormality
- H6 Compressor position sensor abnormality (start failure)
- H9 Outdoor air thermistor fault
- J3 Discharge pipe thermistor fault
- J6 Outdoor coil thermistor fault
- L3 Electrical box temperature rise
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Daikin FTX-W service manual SiUS042228E, Troubleshooting 4.22, p.101. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.