Daikin · Mini-split
L3 Electrical box temperature rise
What the control is telling you
With the compressor off, radiation fin temperature is above 92 C (197.6 F). Clears below 70 C (158 F). The outdoor fan runs to cool the board above 77 C (170.6 F) and stops below 70 C.
Applies to: FTX30/36WVJU9 with RX30/36WMVJU9 or RK30/36WMVJU9
Likely causes
- Faulty outdoor fan motor
- Blocked airflow or short cycling
- Faulty fin thermistor
- Connector off
- Faulty outdoor PCB
Test and repair steps
- Turn off power at the disconnect before opening the unit or touching connectors. Clean the radiation fin if dirty.
- Check the installation (check no. 17) and outdoor fan (check no. 19).
- Fix loose connectors or fan leads, replace the fan motor if bad, otherwise replace the outdoor main PCB.
Models that show this code
6 models in Daikin FTX-W
Other codes on the same units
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Daikin FTX-W service manual SiUS042228E, Troubleshooting 4.24, p.105. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.