Daikin · Mini-split

L4 Radiation fin temperature rise

High severity Daikin FTX-W

What the control is telling you

With the compressor on, fin temperature is above 82 C (179.6 F). Clears below 77 C (170.6 F). Repeats lead to shutdown. Resets after about 60 minutes of error-free running.

Applies to: FTX30/36WVJU9 with RX30/36WMVJU9 or RK30/36WMVJU9

Likely causes

  • Faulty outdoor fan motor
  • Blocked airflow
  • Faulty fin thermistor
  • Connector off
  • Faulty outdoor PCB
  • No silicone grease on the fin after a PCB swap

Test and repair steps

  1. Turn off power at the disconnect before opening the unit or touching connectors. Clean the radiation fin if dirty.
  2. If the PCB was replaced, confirm silicone grease is applied on the fin.
  3. Check the installation (check no. 17) and outdoor fan (check no. 19).
  4. Replace the outdoor main PCB if the error returns.

Models that show this code

6 models in Daikin FTX-W

FTX30WVJU9FTX36WVJU9RK30WMVJU9RK36WMVJU9RX30WMVJU9RX36WMVJU9

Other codes on the same units

  • H9 Outdoor air thermistor fault
  • J3 Discharge pipe thermistor fault
  • J6 Outdoor coil thermistor fault
  • L3 Electrical box temperature rise
  • L5 Output overcurrent
  • P4 Radiation fin thermistor fault
  • U0 Refrigerant shortage
  • U2 Low or high supply voltage detected

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Daikin FTX-W service manual SiUS042228E, Troubleshooting 4.25, p.106. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.