Daikin · Mini-split

U2 Low or high supply voltage detected

High severity Daikin FTX-W

What the control is telling you

Indoor PCB flags it when it sees no zero-cross signal for about 10 seconds. Outdoor PCB flags it when DC bus voltage drops below roughly 150 to 200 V or an over-voltage signal is raised. The compressor stops and restarts after a 3 minute wait.

Applies to: FTX30/36WVJU9 with RX30/36WMVJU9 or RK30/36WMVJU9

Likely causes

  • Supply voltage out of spec
  • Momentary voltage drop or power failure
  • Electrical noise
  • Compressor harness loose
  • Shorted outdoor fan motor winding
  • Faulty DC voltage detection, over-voltage detection or PAM circuit
  • Faulty outdoor PCB
  • Faulty indoor PCB

Test and repair steps

  1. Turn off power at the disconnect before opening the unit or touching connectors. Check the supply voltage is within 10% of rated.
  2. Check the compressor harness is tight.
  3. Wait at least 30 seconds after power off, then restart. Repeat a few times.
  4. If it returns within 3 minutes of power on, spin the outdoor fan by hand. If it does not turn freely, replace the fan motor and the outdoor main PCB.
  5. If it does not return quickly, watch the unit for a long period for noise or power distortion.
  6. If the fault stays, replace the outdoor main PCB, then the indoor control PCB.

Models that show this code

6 models in Daikin FTX-W

FTX30WVJU9FTX36WVJU9RK30WMVJU9RK36WMVJU9RX30WMVJU9RX36WMVJU9

Other codes on the same units

  • L4 Radiation fin temperature rise
  • L5 Output overcurrent
  • P4 Radiation fin thermistor fault
  • U0 Refrigerant shortage
  • U4 Indoor to outdoor signal error
  • U7 Outdoor PCB internal communication error
  • EA Four way valve abnormality
  • UA Indoor and outdoor unit mismatch

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Daikin FTX-W service manual SiUS042228E, Troubleshooting 4.6, p.76. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.