Daikin · Mini-split

U7 Outdoor PCB internal communication error

High severity Daikin FTX-W

What the control is telling you

The main microcomputer cannot get data from the power module side (PM1) for 9 seconds.

Applies to: FTX30/36WVJU9 with RX30/36WMVJU9 or RK30/36WMVJU9

Likely causes

  • Faulty outdoor main PCB

Test and repair steps

  1. Turn off power at the disconnect before opening the unit or touching connectors. Power the unit off and on again.
  2. If the error returns, replace the outdoor main PCB.
  3. If it does not return, treat it as an outside influence and watch the unit over time.

Models that show this code

6 models in Daikin FTX-W

FTX30WVJU9FTX36WVJU9RK30WMVJU9RK36WMVJU9RX30WMVJU9RX36WMVJU9

Other codes on the same units

  • L4 Radiation fin temperature rise
  • L5 Output overcurrent
  • P4 Radiation fin thermistor fault
  • U0 Refrigerant shortage
  • U2 Low or high supply voltage detected
  • U4 Indoor to outdoor signal error
  • EA Four way valve abnormality
  • UA Indoor and outdoor unit mismatch

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Daikin FTX-W service manual SiUS042228E, Troubleshooting 4.8, p.80. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.