Daikin · Mini-split
U4 Indoor to outdoor signal error
What the control is telling you
The indoor unit cannot receive valid data from the outdoor unit.
Applies to: FTX30/36WVJU9 with RX30/36WMVJU9 or RK30/36WMVJU9
Likely causes
- Supply voltage out of spec or sagging
- Wiring error or broken interconnect wire (wire No. 3)
- Shorted outdoor fan motor winding
- Distorted supply waveform
- Faulty outdoor PCB
- Faulty indoor PCB
Test and repair steps
- Turn off power at the disconnect before opening the unit or touching connectors. Check supply voltage is within 10% of rated.
- Wait 15 seconds after power on, start fan mode from the remote to cancel standby saving, then look at LED A on the outdoor PCB.
- LED A blinking check the interconnect wires for wiring errors and insulation damage, and measure voltage on the indoor terminals between 1 and 3 and between 2 and 3. If wiring is good, check the supply waveform (check no. 11) and replace the indoor PCB.
- LED A steady on or off spin the outdoor fan by hand. If it is not smooth, replace the fan motor and outdoor main PCB. Otherwise replace the outdoor main PCB and the interconnect wires.
Models that show this code
6 models in Daikin FTX-W
Other codes on the same units
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Daikin FTX-W service manual SiUS042228E, Troubleshooting 4.7, p.78. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.