L5 Output overcurrent

High severity Daikin FTX-W

What the control is telling you

Triggered by a position signal error, a speed error, or the output overcurrent circuit while the compressor runs. Repeats lead to shutdown. Resets after about 11 minutes of error-free running. Shows only on system shutdown.

Applies to: FTX30/36WVJU9 with RX30/36WMVJU9 or RK30/36WMVJU9

Likely causes

  • Poor installation
  • Closed stop valve
  • Faulty power module
  • Wrong internal wiring
  • Supply voltage problem
  • Faulty compressor
  • Faulty outdoor PCB

Test and repair steps

  1. Turn off power at the disconnect before opening the unit or touching connectors. Open the stop valve fully.
  2. If parts were swapped, check internal wiring again.
  3. Check supply voltage within 10% of rated.
  4. Run the inverter analyzer with U, V, W disconnected (check no. 15) and check the power module (check no. 22).
  5. Check the compressor windings for shorts or breaks.
  6. Check the installation (check no. 17) and discharge pressure (check no. 18).

Models that show this code

6 models in Daikin FTX-W

FTX30WVJU9FTX36WVJU9RK30WMVJU9RK36WMVJU9RX30WMVJU9RX36WMVJU9

Other codes on the same units

  • J3 Discharge pipe thermistor fault
  • J6 Outdoor coil thermistor fault
  • L3 Electrical box temperature rise
  • L4 Radiation fin temperature rise
  • P4 Radiation fin thermistor fault
  • U0 Refrigerant shortage
  • U2 Low or high supply voltage detected
  • U4 Indoor to outdoor signal error

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Daikin FTX-W service manual SiUS042228E, Troubleshooting 4.26, p.108. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.