Daikin · Mini-split

J3 Discharge pipe thermistor fault

Medium severity Daikin FTX-W

What the control is telling you

The discharge pipe thermistor input reads 4.96 V or more, or 0.04 V or less, with power on. J3 is also set when the discharge temperature reads lower than the coil temperature. Shows only on system shutdown.

Applies to: FTX30/36WVJU9 with RX30/36WMVJU9 or RK30/36WMVJU9

Likely causes

  • Connector not seated
  • Faulty thermistor
  • Faulty outdoor PCB
  • Faulty coil thermistor used for the comparison

Test and repair steps

  1. Turn off power at the disconnect before opening the unit or touching connectors. Reseat the thermistor connector.
  2. Measure the thermistor resistance (check no. 01) and replace bad ones.
  3. For J3, also check the coil thermistor used for the comparison (outdoor coil in cooling, indoor coil in heating).
  4. If the error returns and the sensors are good, replace the outdoor main PCB.

Models that show this code

6 models in Daikin FTX-W

FTX30WVJU9FTX36WVJU9RK30WMVJU9RK36WMVJU9RX30WMVJU9RX36WMVJU9

Other codes on the same units

  • H0 Compressor current sensor abnormality
  • H6 Compressor position sensor abnormality (start failure)
  • H8 Current transformer (CT) abnormality
  • H9 Outdoor air thermistor fault
  • J6 Outdoor coil thermistor fault
  • L3 Electrical box temperature rise
  • L4 Radiation fin temperature rise
  • L5 Output overcurrent

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Daikin FTX-W service manual SiUS042228E, Troubleshooting 4.23, p.103. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.