EA Four way valve abnormality
What the control is telling you
Room and indoor coil temperatures do not move the right way. Cooling or dry: room minus coil temperature below -5 C (-9 F). Heating: coil minus room below -5 C (-9 F). Condition must hold 10 minutes after 5 minutes of running. Repeats lead to shutdown. Resets after about 60 minutes of error-free running.
Applies to: FTX30/36WVJU9 with RX30/36WMVJU9 or RK30/36WMVJU9
Likely causes
- Four way valve coil loose
- Faulty valve, coil or harness
- Faulty outdoor PCB
- Faulty thermistor
- Refrigerant shortage
- Moisture in refrigerant
- Faulty stop valve
Test and repair steps
- Turn off power at the disconnect before opening the unit or touching connectors. Check the coil seating and harness. Coil resistance should be about 1000 to 2000 ohms by the flowchart, and 520 to 580 ohms in check no. 13.
- Check the thermistors (check no. 01).
- Run the four way valve check (check no. 13).
- Check the refrigerant line (check no. 14).
- Replace the outdoor PCB if the valve gets no drive signal.
Models that show this code
6 models in Daikin FTX-W
Other codes on the same units
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Daikin FTX-W service manual SiUS042228E, Troubleshooting 4.16, p.91. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.