Daikin · Mini-split

EA Four way valve abnormality

High severity Daikin FTX-W

What the control is telling you

Room and indoor coil temperatures do not move the right way. Cooling or dry: room minus coil temperature below -5 C (-9 F). Heating: coil minus room below -5 C (-9 F). Condition must hold 10 minutes after 5 minutes of running. Repeats lead to shutdown. Resets after about 60 minutes of error-free running.

Applies to: FTX30/36WVJU9 with RX30/36WMVJU9 or RK30/36WMVJU9

Likely causes

  • Four way valve coil loose
  • Faulty valve, coil or harness
  • Faulty outdoor PCB
  • Faulty thermistor
  • Refrigerant shortage
  • Moisture in refrigerant
  • Faulty stop valve

Test and repair steps

  1. Turn off power at the disconnect before opening the unit or touching connectors. Check the coil seating and harness. Coil resistance should be about 1000 to 2000 ohms by the flowchart, and 520 to 580 ohms in check no. 13.
  2. Check the thermistors (check no. 01).
  3. Run the four way valve check (check no. 13).
  4. Check the refrigerant line (check no. 14).
  5. Replace the outdoor PCB if the valve gets no drive signal.

Models that show this code

6 models in Daikin FTX-W

FTX30WVJU9FTX36WVJU9RK30WMVJU9RK36WMVJU9RX30WMVJU9RX36WMVJU9

Other codes on the same units

  • L4 Radiation fin temperature rise
  • L5 Output overcurrent
  • P4 Radiation fin thermistor fault
  • U0 Refrigerant shortage
  • U2 Low or high supply voltage detected
  • U4 Indoor to outdoor signal error
  • U7 Outdoor PCB internal communication error
  • UA Indoor and outdoor unit mismatch

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Daikin FTX-W service manual SiUS042228E, Troubleshooting 4.16, p.91. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.