Daikin · Heat pump
CC Humidity sensor abnormality (communication or malfunction)
What the control is telling you
Shares the same troubleshooting path as C9. The indoor unit detects a communication error with the humidity sensor or a malfunction of the humidity sensor.
Applies to: FTXM-W/V wall mounted inverter heat pump, indoor unit
Likely causes
- Disconnected connector
- Faulty humidity sensor
- Faulty indoor unit PCB
Test and repair steps
- Turn off the power before connecting or disconnecting connectors.
- Check the connection of the connectors and reconnect them firmly.
- Restore power and check whether the error code is still displayed.
- If the error remains, replace the humidity sensor PCB.
- If the error still remains after that, replace the control PCB and confirm the fault is cleared.
Other codes on the same units
- C9 Room temperature sensor / humidity sensor abnormality (communication or malfunction)
- F6 High pressure control in cooling
- F8 Compressor temperature abnormality (discharge pipe)
- H0 Compressor system sensor abnormality
- H6 Position sensor abnormality (compressor start-up failure)
- H8 DC voltage/current sensor abnormality
- U0 Refrigerant shortage
- U2 Low-voltage or over-voltage detection
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: SiUS042113EA service manual, p. 108. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.