Daikin · Heat pump
H0 Compressor system sensor abnormality
What the control is telling you
The system checks the DC current before compressor start. Fault is declared when the converted voltage is outside 0.5 to 4.5 V, or when the DC voltage before start is below 50 V.
Applies to: FTXM-W/V outdoor unit, compressor start
Likely causes
- Broken or disconnected harness
- Defective outdoor unit PCB
Test and repair steps
- Turn off the power, then turn it on again to restart the system.
- If the error does not return, it is not a malfunction; keep observing.
- If the error returns, check whether the relay harness for the compressor is broken.
- Replace the harness if it is broken.
- If the harness is good and the error persists, replace the outdoor unit PCB (main PCB).
Other codes on the same units
- C9 Room temperature sensor / humidity sensor abnormality (communication or malfunction)
- F6 High pressure control in cooling
- F8 Compressor temperature abnormality (discharge pipe)
- H6 Position sensor abnormality (compressor start-up failure)
- H8 DC voltage/current sensor abnormality
- U0 Refrigerant shortage
- U2 Low-voltage or over-voltage detection
- CC Humidity sensor abnormality (communication or malfunction)
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: SiUS042113EA service manual, p. 132. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.