Daikin · Heat pump

U0 Refrigerant shortage

High severity FTXM-W/V

What the control is telling you

The control board detects low refrigerant using three checks: input current versus compressor frequency, discharge pipe temperature with expansion valve opening, and the temperature difference across the system. A fault is set when the conditions hold for the set time. After repeated errors the system shuts down. It resets after about 60 minutes of continuous running without other errors.

Applies to: FTXM-W/V wall mounted inverter heat pump, outdoor unit refrigerant circuit

Likely causes

  • Refrigerant leak or insufficient charge
  • Oil leak at internal piping or relay pipe connections
  • Outdoor stop valve closed
  • Pipe flare leak or cracked pipe
  • Harness rubbing against piping
  • Disconnected or faulty thermistor
  • Faulty power transistor harness connection
  • Compressor vibrating excessively

Test and repair steps

  1. Check the system for refrigerant shortage.
  2. If short, add the specified amount of fresh refrigerant.
  3. Reconnect any disconnected thermistors.
  4. Make sure the stop valve is fully open.
  5. Check for oil leaks at internal piping and relay pipe connections; repair pipe flares or replace unions as needed.
  6. Check whether any harness touches the piping and correct it. Replace any cracked pipes.
  7. Check the power transistor harness connection.
  8. Replace any defective thermistor.
  9. If the error returns, replace the outdoor unit PCB (main PCB).
  10. If the error still returns after that, replace the compressor.

Other codes on the same units

  • C9 Room temperature sensor / humidity sensor abnormality (communication or malfunction)
  • F6 High pressure control in cooling
  • F8 Compressor temperature abnormality (discharge pipe)
  • H0 Compressor system sensor abnormality
  • H6 Position sensor abnormality (compressor start-up failure)
  • H8 DC voltage/current sensor abnormality
  • U2 Low-voltage or over-voltage detection
  • CC Humidity sensor abnormality (communication or malfunction)

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: SiUS042113EA service manual, p. 109-110. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.