Daikin · Heat pump
U2 Low-voltage or over-voltage detection
What the control is telling you
Low voltage is detected by the DC voltage detection circuit on the indoor and outdoor units. Over-voltage is detected by a separate circuit on the outdoor unit. On the outdoor unit the compressor stops and restarts automatically after a 3-minute standby.
Applies to: FTXM-W/V wall mounted inverter heat pump, indoor and outdoor units
Likely causes
- Power supply voltage out of specification
- Faulty DC voltage or over-voltage detection circuit
- Faulty PAM control part
- Disconnected compressor harness
- Short inside the fan motor winding
- Noise or momentary voltage drop or power failure
- Faulty outdoor unit PCB
- Faulty indoor unit PCB
Test and repair steps
- Check the power supply voltage. It should be within ±10% of the rated value.
- If the voltage is out of range, correct the power supply.
- Check the compressor harness connection and reconnect it if loose or disconnected.
- Check whether the outdoor fan turns smoothly. If not, replace the outdoor fan motor and the outdoor unit PCB (main PCB).
- Turn off the power and wait at least 30 seconds before turning it back on.
- Restore power and check whether the system restarts. Repeat a few times.
- If the error returns within 3 minutes of power-on, replace the indoor unit PCB (control PCB).
- If the error still occurs, replace the outdoor unit PCB (main PCB).
- If the fault seems intermittent, check for noise or power supply distortion over the long term.
Other codes on the same units
- C9 Room temperature sensor / humidity sensor abnormality (communication or malfunction)
- F6 High pressure control in cooling
- F8 Compressor temperature abnormality (discharge pipe)
- H0 Compressor system sensor abnormality
- H6 Position sensor abnormality (compressor start-up failure)
- H8 DC voltage/current sensor abnormality
- U0 Refrigerant shortage
- CC Humidity sensor abnormality (communication or malfunction)
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: SiUS042113EA service manual, p. 111-112. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.