Daikin · Heat pump
H6 Position sensor abnormality (compressor start-up failure)
What the control is telling you
A compressor start-up failure is detected by checking compressor running through the position detection circuit. If the error repeats, the system shuts down. Reset occurs after about 11 minutes of continuous running with no other error.
Applies to: FTXM-W/V outdoor unit, compressor start-up
Likely causes
- Power supply voltage out of specification
- Disconnected compressor harness
- Defective compressor
- Defective outdoor unit PCB
- Start-up failure caused by a closed stop valve
- Input voltage outside the specified range
Test and repair steps
- Turn off the power and check all connections.
- Check the power supply voltage; it must be within ±10% of the rated value. Correct the supply if it is not.
- Check for a short circuit in the diode bridge (Check No. 20, p. 149).
- Check with the inverter analyzer (Check No. 15, p. 145; analyzer part RSUK0917C).
- Turn off the power, disconnect harnesses U, V and W, turn the power on and check the electrolytic capacitor voltage (the flowchart indicates it should be within 320 VDC).
- Check the discharge pressure (Check No. 18, p. 149); replace the stop valve if it is not OK.
- Reconnect the electrical components and compressor harnesses as specified.
- If the compressor is faulty, replace the compressor.
- If the fault remains, replace the outdoor unit PCB (main PCB).
Other codes on the same units
- C9 Room temperature sensor / humidity sensor abnormality (communication or malfunction)
- F6 High pressure control in cooling
- F8 Compressor temperature abnormality (discharge pipe)
- H0 Compressor system sensor abnormality
- H8 DC voltage/current sensor abnormality
- U0 Refrigerant shortage
- U2 Low-voltage or over-voltage detection
- CC Humidity sensor abnormality (communication or malfunction)
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: SiUS042113EA service manual, p. 133-134. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.