Daikin · Heat pump

C9 Room temperature sensor / humidity sensor abnormality (communication or malfunction)

Medium severity FTXM-W/V

What the control is telling you

The indoor unit detects a communication error with the humidity sensor or a malfunction of the humidity sensor, based on the input value.

Applies to: FTXM-W/V wall mounted inverter heat pump, indoor unit

Likely causes

  • Disconnected connector
  • Faulty humidity sensor
  • Faulty indoor unit PCB

Test and repair steps

  1. Turn off the power before connecting or disconnecting connectors.
  2. Check the connection of the connectors and reconnect them firmly.
  3. Restore power and check whether the error code is still displayed.
  4. If the error remains, replace the humidity sensor PCB.
  5. If the error still remains after that, replace the control PCB and confirm the fault is cleared.

Other codes on the same units

  • A6 Indoor fan motor (DC motor) abnormality
  • C4 Indoor heat exchanger thermistor abnormality
  • F6 High pressure control in cooling
  • F8 Compressor temperature abnormality (discharge pipe)
  • H0 Compressor system sensor abnormality
  • H6 Position sensor abnormality (compressor start-up failure)
  • H8 DC voltage/current sensor abnormality
  • U0 Refrigerant shortage

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: SiUS042113EA service manual, p. 108. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.