Daikin · Heat pump

A6 Indoor fan motor (DC motor) abnormality

Medium severity FTXM-W/V

What the control is telling you

The control board monitors indoor fan speed. The fault is set when the fan does not reach the demanded speed for the selected tap and runs below 50% of its maximum speed, or when the fan does not turn for more than 5 seconds after starting.

Applies to: FTXM-W/V wall mounted inverter heat pump, indoor unit

Likely causes

  • Large drop in power supply voltage
  • Short between turns inside the fan motor winding
  • Broken wire inside the fan motor
  • Broken fan motor lead wires
  • Faulty fan motor capacitor
  • Faulty indoor unit PCB

Test and repair steps

  1. Turn off the power before touching any connector.
  2. Check that the fan motor connector is fully seated; disconnect and reconnect it to make sure.
  3. Remove any foreign matter in or around the fan.
  4. Turn the fan by hand. It should turn smoothly and without abnormal noise.
  5. If the fan is stiff or noisy, check the rubber cushions. Refit or replace them as needed.
  6. Check the fan motor for breakdown or short circuit, and measure winding resistance (Check No. 03, P.142 in the manual, not included here).
  7. If the motor is faulty, replace the indoor fan motor. If the motor is good, replace the indoor unit PCB.
  8. Do not disconnect the motor connector with power on; the motor may be damaged.

Other codes on the same units

  • C4 Indoor heat exchanger thermistor abnormality
  • C9 Room temperature sensor / humidity sensor abnormality (communication or malfunction)
  • F6 High pressure control in cooling
  • F8 Compressor temperature abnormality (discharge pipe)
  • H0 Compressor system sensor abnormality
  • H6 Position sensor abnormality (compressor start-up failure)
  • H8 DC voltage/current sensor abnormality
  • U0 Refrigerant shortage

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: SiUS042113EA service manual, p. 105-106. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.