Daikin · Heat pump
C4 Indoor heat exchanger thermistor abnormality
What the control is telling you
The voltage across the indoor heat exchanger thermistor is outside the valid range (too high or too low) with power on. The thermistor circuit is considered faulty.
Applies to: FTXM-W/V wall mounted inverter heat pump, indoor unit
Likely causes
- Disconnected connector
- Faulty thermistor
- Faulty indoor unit PCB
Test and repair steps
- Turn off the power before connecting or disconnecting connectors.
- Check that the thermistor connector is correctly connected; correct it if loose.
- Measure the thermistor resistance (Check No. 01, P.141 in the manual, not included here). If it is out of range, replace the thermistor.
- If the thermistor reads normal, replace the indoor unit PCB (control PCB).
Other codes on the same units
- A6 Indoor fan motor (DC motor) abnormality
- C9 Room temperature sensor / humidity sensor abnormality (communication or malfunction)
- F6 High pressure control in cooling
- F8 Compressor temperature abnormality (discharge pipe)
- H0 Compressor system sensor abnormality
- H6 Position sensor abnormality (compressor start-up failure)
- H8 DC voltage/current sensor abnormality
- U0 Refrigerant shortage
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: SiUS042113EA service manual, p. 107. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.