Daikin · Heat pump

CoreSense 1 CoreSense: yellow 1 flash, long run time

Medium severity Daikin R-32 DH4S/DH5S

What the control is telling you

Yellow ALERT, 1 flash: the compressor has run more than 18 hours straight, which points to low capacity from a low side problem. No lockout. Code 1 is turned off in heat pump mode.

Applies to: DH4SQA, DH4SEA, DH5SEA (single stage R-32 heat pumps with CoreSense module)

Likely causes

  • Low charge
  • Indoor blower not running (relay, capacitor, motor, wiring, indoor board, open thermostat wire)
  • Frozen indoor coil (low suction, thermostat set very low, dirty filter or coil, blocked ducts or registers)
  • Bad metering device (TXV bulb or stuck TXV / orifice)
  • Liquid line restriction or blocked filter drier
  • Bad thermostat (shorted sub-base or wiring, poor location)

Test and repair steps

  1. Kill power at the disconnect before working in the unit. There can be more than one power source.
  2. Make sure the indoor blower runs and check its relay, capacitor, motor and wiring.
  3. Check the filter, indoor coil, ducts and registers. Thaw the coil if frozen.
  4. Check suction pressure and the charge.
  5. Check the TXV bulb and whether the TXV or orifice is stuck.
  6. Check for a liquid line restriction or blocked drier.
  7. Check the thermostat setting, wiring and location.

Models that show this code

3 models in Daikin R-32 DH4S/DH5S

DH4SEA**10AADH4SQA**10AADH5SEA**10AA

Other codes on the same units

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Daikin RSD6200301 Service and Troubleshooting, DC3S/DC4S/DC5S AC and DH4S/DH5S heat pump R-32 (07-2024), Diagnostics Table: CoreSense Module p.20-21 and Table 1 Quick Reference p.22. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.