Daikin · Heat pump
CoreSense TRIP+ALERT flashing CoreSense: TRIP and ALERT flashing together
What the control is telling you
TRIP and ALERT LEDs flashing at the same time: control voltage is too low for the module to run.
Applies to: DH4SQA, DH4SEA, DH5SEA (single stage R-32 heat pumps with CoreSense module)
Likely causes
- Low control circuit voltage
Test and repair steps
- Kill power at the disconnect before working in the unit. There can be more than one power source.
- Measure 24 V at the module and at the transformer. Find the cause of the low control voltage (transformer, wiring, overloaded circuit).
Models that show this code
3 models in Daikin R-32 DH4S/DH5S
Other codes on the same units
- CoreSense 1 CoreSense: yellow 1 flash, long run time
- CoreSense 2 CoreSense: 2 flashes, pressure trip (yellow alert / red lock)
- CoreSense 3 CoreSense: 3 flashes, short cycling (yellow alert / red lock)
- CoreSense 4 CoreSense: 4 flashes, locked rotor (yellow alert / red lock)
- CoreSense 5 CoreSense: 5 flashes, moderate run trip (yellow alert / red lock)
- CoreSense 9 CoreSense: red 9 flashes, PROT terminal over current
- CoreSense solid red CoreSense: solid red TRIP
- CoreSense solid yellow CoreSense: solid yellow RUN
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Daikin RSD6200301 Service and Troubleshooting, DC3S/DC4S/DC5S AC and DH4S/DH5S heat pump R-32 (07-2024), Diagnostics Table: CoreSense Module p.20-21 and Table 1 Quick Reference p.22. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.