Daikin · Heat pump

CoreSense 4 CoreSense: 4 flashes, locked rotor (yellow alert / red lock)

High severity Daikin R-32 DH4S/DH5S

What the control is telling you

Code 4: the compressor trips within 12 seconds of starting and does not start again within 35 seconds. Yellow 4 flashes = alert. Red 4 flashes with yellow off = locked out after 10 in a row.

Applies to: DH4SQA, DH4SEA, DH5SEA (single stage R-32 heat pumps with CoreSense module)

Likely causes

  • Run capacitor failed
  • Low line voltage or bad wiring connections
  • Too much liquid refrigerant in the compressor
  • Seized compressor bearings

Test and repair steps

  1. Kill power at the disconnect before working in the unit. There can be more than one power source.
  2. Test the run capacitor. Replace it if it is out of spec.
  3. Measure line voltage at the disconnect while starting. If it is low there, the utility has to look at it.
  4. Check the wiring connections.
  5. Look for liquid refrigerant in the compressor.
  6. Check the compressor oil level. A seized compressor has to be replaced.
  7. After the fix, press the module reset to clear a lockout.

Models that show this code

3 models in Daikin R-32 DH4S/DH5S

DH4SEA**10AADH4SQA**10AADH5SEA**10AA

Other codes on the same units

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Daikin RSD6200301 Service and Troubleshooting, DC3S/DC4S/DC5S AC and DH4S/DH5S heat pump R-32 (07-2024), Diagnostics Table: CoreSense Module p.20-21 and Table 1 Quick Reference p.22. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.