Daikin · Heat pump

CoreSense 5 CoreSense: 5 flashes, moderate run trip (yellow alert / red lock)

High severity Daikin R-32 DH4S/DH5S

What the control is telling you

Code 5: the compressor ran 15 minutes to 18 hours, then tripped for more than 7 minutes. Yellow 5 flashes = alert. Red 5 flashes with yellow off = locked out after 4 in a row or 10 total.

Applies to: DH4SQA, DH4SEA, DH5SEA (single stage R-32 heat pumps with CoreSense module)

Likely causes

  • Indoor blower not running: blower relay coil or contacts, blower capacitor, failed or blocked motor, blower wiring, indoor control board, or an open thermostat wire
  • Bad metering device: TXV bulb wrong size, spot or contact, or TXV / fixed orifice stuck closed
  • Dirty, blocked or damaged outdoor coil
  • Low charge

Test and repair steps

  1. Kill power at the disconnect before working in the unit. There can be more than one power source.
  2. Make sure the indoor blower runs. Check the blower relay, capacitor, motor, wiring and the indoor control board.
  3. Check the thermostat wiring for an open.
  4. Check the TXV bulb (size, location, contact) and whether the TXV or orifice is stuck closed.
  5. Clean the outdoor coil.
  6. Check the charge.
  7. After the fix, press the module reset to clear a lockout.

Models that show this code

3 models in Daikin R-32 DH4S/DH5S

DH4SEA**10AADH4SQA**10AADH5SEA**10AA

Other codes on the same units

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Daikin RSD6200301 Service and Troubleshooting, DC3S/DC4S/DC5S AC and DH4S/DH5S heat pump R-32 (07-2024), Diagnostics Table: CoreSense Module p.20-21 and Table 1 Quick Reference p.22. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.