Daikin · Heat pump
CoreSense 5 CoreSense: 5 flashes, moderate run trip (yellow alert / red lock)
What the control is telling you
Code 5: the compressor ran 15 minutes to 18 hours, then tripped for more than 7 minutes. Yellow 5 flashes = alert. Red 5 flashes with yellow off = locked out after 4 in a row or 10 total.
Applies to: DH4SQA, DH4SEA, DH5SEA (single stage R-32 heat pumps with CoreSense module)
Likely causes
- Indoor blower not running: blower relay coil or contacts, blower capacitor, failed or blocked motor, blower wiring, indoor control board, or an open thermostat wire
- Bad metering device: TXV bulb wrong size, spot or contact, or TXV / fixed orifice stuck closed
- Dirty, blocked or damaged outdoor coil
- Low charge
Test and repair steps
- Kill power at the disconnect before working in the unit. There can be more than one power source.
- Make sure the indoor blower runs. Check the blower relay, capacitor, motor, wiring and the indoor control board.
- Check the thermostat wiring for an open.
- Check the TXV bulb (size, location, contact) and whether the TXV or orifice is stuck closed.
- Clean the outdoor coil.
- Check the charge.
- After the fix, press the module reset to clear a lockout.
Models that show this code
3 models in Daikin R-32 DH4S/DH5S
Other codes on the same units
- CoreSense 1 CoreSense: yellow 1 flash, long run time
- CoreSense 2 CoreSense: 2 flashes, pressure trip (yellow alert / red lock)
- CoreSense 3 CoreSense: 3 flashes, short cycling (yellow alert / red lock)
- CoreSense 4 CoreSense: 4 flashes, locked rotor (yellow alert / red lock)
- CoreSense 9 CoreSense: red 9 flashes, PROT terminal over current
- CoreSense TRIP+ALERT flashing CoreSense: TRIP and ALERT flashing together
- CoreSense solid red CoreSense: solid red TRIP
- CoreSense solid yellow CoreSense: solid yellow RUN
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Daikin RSD6200301 Service and Troubleshooting, DC3S/DC4S/DC5S AC and DH4S/DH5S heat pump R-32 (07-2024), Diagnostics Table: CoreSense Module p.20-21 and Table 1 Quick Reference p.22. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.