Rheem · Furnace · Heating

Two-stage heating cycle and staging

RGPE two-stage (IFC with spark)

What happens, in order

  1. 24 V signal on W (or a communicating heat message) starts the cycle
  2. Control checks high and low pressure switches are open
  3. Inducer starts on high speed for a 30 s pre-purge; pressure switches close as it builds vacuum
  4. Spark fires and the main valve opens on low fire; ignition control drops out once flame is proven (8 s maximum trial)
  5. Gas valve stays on low rate through the 20 s warm-up before the blower takes over
  6. Two-stage thermostat (SW1-3 off) W only = low gas pressure and low blower speed; W2 = high gas pressure and high blower speed
  7. Single-stage thermostat (SW2-2 and SW2-3 off): low fire for 0 to 7 minutes, then 100 percent firing
  8. If the call ends during any phase the furnace shuts down at the rate it was running
  9. Heat call removed furnace returns to the normal off cycle

Timings and thresholds

ItemValue
Pre-purge30 s
Trial for ignition8 s max
Warm-up on low rate before blower20 s
Single-stage thermostat low-to-high timer7 min

Applies to: Rheem RGPE series

Models

RGPE series

More Rheem furnace sequences

Take it to the job

Sequences of operation, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Rheem RGPE series installation manual, Sequence of Operation (Heating Cycle Initiation / Response / Termination). Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.