NTI · Boiler · Other

Lead-lag (cascade) demand handling

Trinity Tft

What happens, in order

  1. Up to 8 boilers share a primary/secondary loop and are linked by three-wire communication (DATA+, DATA-, DATA COM)
  2. One boiler is set as master and becomes the single contact point for central heat and outdoor reset settings and system control wiring
  3. Central heat call from the master's CH2 (LL) input; the system sensor, when fitted, becomes the modulation sensor
  4. The master stages the other boilers and each boiler runs its own boiler pump from PUMP B
  5. One boiler can run the shared CH pump on PUMP C and one the DHW pump on PUMP A for master demands
  6. Each boiler must have its own Modbus address from 1 to 8

Codes you may see during this

Alert 206 Alert 233

Applies to: Trinity Tft60, Tft85, Tft110, Tft155, Tft175, Tft200, Tft250, Tft300, Tft399

Models

Tft60Tft85Tft110Tft155Tft175Tft200Tft250Tft300Tft399

More NTI boiler sequences

Take it to the job

Sequences of operation, error codes and tips work offline in the HVACopedia app.

Open the app

Source: NTI Tft60-399 Installation and Operation Instructions (rev. 2012-04-09), Sec. 8.0 Lighting, Sec. 10.0 Piping, Sec. 15.0 Troubleshooting. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.