NTI · Boiler · Startup

Combustion checking procedure

TRX

What happens, in order

  1. Operation 1 Connect a manometer to the line pressure test port (Torx 10 screw 1). Enable Test Mode by holding RESET for 10 seconds and check gas inlet pressure against the table for the gas type under all operating conditions.
  2. Operation 2 Remove the combustion test port plug and insert a calibrated combustion analyzer.
  3. Operation 3 Create a heat demand at the highest setting or maximum DHW draw. Activate the TEST function by holding RESET for 10 seconds, then press the button for maximum power. Wait 1 minute and read CO2 and CO. Adjust the max gas valve setting screw 4 (clockwise raises CO2, about 0.3% per turn) if needed.
  4. Operation 4 With the TEST function active, select minimum power and wait 1 minute. If min CO2 is higher than max CO2, or lower by more than 0.3%, adjust screw 2 (counter-clockwise lowers CO2, clockwise raises it). If min CO2 changes, repeat the max adjustment.
  5. Operation 5 Exit Test Mode by pressing RESET. Turn down the thermostat or stop DHW draw. Reset thermostatic valves in heating-only systems. Check for gas leaks, reinstall the front cover, and reinstall the combustion test port.

Timings and thresholds

ItemValue
Test Function auto shutoff30 minutes
Stabilize time after each change1 minute
Test Mode / Test Function activationhold RESET 10 seconds

Applies to: TRX150 and related TRX models

Models

TRX150TRX199TRX199C

More NTI boiler sequences

Take it to the job

Sequences of operation, error codes and tips work offline in the HVACopedia app.

Open the app

Source: NTI TRX150 manual, p. 78-79. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.