NTI · Boiler · Ignition
First ignition start-up
What happens, in order
- Confirm the gas valve is closed and all electrical connections are wired and grounded.
- Confirm system pressure is at least 12 psi on the gauge and no heat or DHW calls are active.
- Power on the boiler with the ON/OFF button. The purge cycle runs automatically.
- Set the room thermostat to the highest setting to start the boiler and test for Error 501.
- After Error 501 appears, set the thermostat to normal.
- Open the gas valve and check all connection seals for leaks.
- Press RESET to clear Error 501.
- Start the boiler by selecting CH or DHW.
- Proceed with the combustion checking procedure.
Timings and thresholds
| Item | Value |
|---|---|
| Initial purge cycle | 7 minutes |
| Combustion fan post-purge before igniter reactivates | at least 5 seconds |
| Failed ignition attempts before lockout | 3 consecutive |
Codes you may see during this
108 501
Applies to: TRX150 and related TRX models
Models
TRX150TRX199TRX199C
More NTI boiler sequences
- Combustion checking procedure · Startup
- Power-on and mode sequence · Startup
- Power-up and what lets the boiler start a call · Startup
- Failed ignition and lockout · Ignition
- Light-off sequence and retries · Ignition
- Central heat call (CH1) from call to satisfied · Heating
- Indirect tank (DHW) call · Domestic hot water
- Circulator outputs and their fuses · Pump/purge
Related
Take it to the job
Sequences of operation, error codes and tips work offline in the HVACopedia app.
Source: NTI TRX150 manual, p. 83. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.