NTI · Boiler · Ignition

First ignition start-up

TRX

What happens, in order

  1. Confirm the gas valve is closed and all electrical connections are wired and grounded.
  2. Confirm system pressure is at least 12 psi on the gauge and no heat or DHW calls are active.
  3. Power on the boiler with the ON/OFF button. The purge cycle runs automatically.
  4. Set the room thermostat to the highest setting to start the boiler and test for Error 501.
  5. After Error 501 appears, set the thermostat to normal.
  6. Open the gas valve and check all connection seals for leaks.
  7. Press RESET to clear Error 501.
  8. Start the boiler by selecting CH or DHW.
  9. Proceed with the combustion checking procedure.

Timings and thresholds

ItemValue
Initial purge cycle7 minutes
Combustion fan post-purge before igniter reactivatesat least 5 seconds
Failed ignition attempts before lockout3 consecutive

Codes you may see during this

108 501

Applies to: TRX150 and related TRX models

Models

TRX150TRX199TRX199C

More NTI boiler sequences

Take it to the job

Sequences of operation, error codes and tips work offline in the HVACopedia app.

Open the app

Source: NTI TRX150 manual, p. 83. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.